Level Transmitters And Switches

ELMLG 100 - Magnetic Liquid Level Gauge

Electronet series Magnetic Liquid Level Gauge ELMLG-100 is an instrument for indicating the fluid level.

It has a magneticfloat inside of the non-magnetic chamber and an indicator outside of it. The indicator indicates the fluid level by means of magnetic force of the magnet installed inside of the float.

The indicator is completely separated from the chamber. The level of liquid and gaseous phases can be distinguished clearly by the Bi-color. Magnetic level indicators are low-maintenance alternatives to sight glasses and other level indicators. They provide non-invasive level indication while reducing leak points and fugitive emissions.

Specification 

 

  • Material: SS316
  • Model: ELMLG-100
  • Brand: ELECTRONET
  • Power Supply: 24 V DC
  • Probe MOC: SS316
  • Process connection: Half inch NPT (F) / Flange
  • Output: 4 to 20 mA / 1 to 5 V 

 

ULT-TX-22 - Two Wire Ultrasonic Level Transmitter

Electronet series ULT-TX-22 is a Two Wire Ultrasonic Level Transmitters specially designed for non contact type level measurement.

Ultrasonic level measurement is based on the time required by ultrasonic pulses to travel from sensor & surface of liquid & back to sensor. Ultrasonic level transmitters are the best for applications such as slurries, corrosive liquids & waste water. The transmitter provides 4-20 mA DC continuous output. The measuring range is available from 0.6 to 6 mtr.

Specification 

 

  • Measuring Range: 0.6 to 6 Meter
  • Power Supply: 24 V DC
  • Power Consumption: 600 mW
  • Measuring Frequency: 25 Khz
  • Protection: IP 66
  • Temperature Coefficient: +- 0.01 % Per Degree C 

 

LMT 01 - Magnetic Float Operated Level Transmitter

Electronet series LMT-01 are Magnetic Float Operated Level Transmitters. The inbuilt level sensor is consisting of a float & guide tube made of non-magnetic material to achieve undisturbed magnetic flux. The float has magnetic system within it & moves along the guide tube which contains glass encapsulated hermitically sealed reed switches. Float follows level & magnetically actuates reed switches & provides continuous 4 - 20 mA DC output.

Specification 

 

  • Response Time: Less than 1000 mSec
  • Accuracy: +/- 10 mm 

 

ELGWR 40 - Guided Wave Level Transmitter

Electronet series ELGWR-40 4-wire TDR-Sensor with single rod or coaxial probe for continuous level measurement and point level detection in liquids, with analog and switching output.

PRODUCT APPLICATION AREA :

The innovative TDR technology enables direct, precise and highly reliable continuous level measurement as well as point level detection in almost every liquid independent of changing process conditions (such as density, conductivity, temperature, pressure, vapour and turbulence). ELGWR-40 has almost no installation restrictions it can be mounted in small tanks, tall and narrow nozzles and it measures precisely even with difficult tank geometries or close to interfering structures. ELGWR-40 is also especially suitable in bypass chambers and stilling wells. It is suitable for all types of processing and storage applications and has an exceptional performance in liquids with low dielectric constant (i.e. low reflectivity) such as oils and hydrocarbons

LCT 01 - Capacitance Level Transmitter

Electronet series LCT-01 are Capacitance Type Level Transmitters. Vessel wall and probe forms two electrodes. If vessel is of non conductive material, the probe will be double rod type.

The distance between electrode and surface area of electrodes remain unchanged. The variable is the depth of the material being measured which represents the dielectric constant between two electrodes. Air and vacuum have relative dielectric constant as 1 and that of liquids, it is greater than 1.

The capacitance of the capacitor therefore depends on how much material lies between the probe and vessel wall i.e. whether the probe is covered with or free from material. The capacitor changes with change in level of the material and provides corresponding 4-20 mA DC continuous output.

Specification 

 

  • Model: LCT-01
  • Color: Blue
  • Isolated Power Supply: 24 V DC, External
  • Process Connection: 1) 1 inch BSP Threaded 2) 1 inch ASA 150, Flanged
  • Accuracy: +/- 1% F. S.
  • Output: 1) 4 to 20 mA DC, 2 Wire 2) 0 - 5 V DC 

 

ELTAR 20 - Through Air Radar Level Transmitter

Electronet series ELTAR-20 Radar Level Transmitter is high frequency level measurement instrument with the maximum measuring distance upto 30 meters. The antenna is further optimized and the new-type microprocessor can perform higher rate of signal analysis and processing, making the instrument available for complex measurement conditions such as reactors and solid silos.

Specification 

 

  • Model: ELTAR-20
  • Accuracy: +/- 0.1% of max. range in lab using 4-20mA current output & +/-0.25%of max. range(typically in field
  • Maximum Pressure: 3 bar
  • Probe MOC: S S316 (For other requirement please consult factory)
  • Conduit Entry: Half inch NPT X 2
  • Operation: Pulse Radar 

 

ULT 200 - Two Wire Ultrasonic Level Transmitter

Electronet series ULT-200 is a Two Wire Ultrasonic Level Transmitters specially designed for non contact type level measurement.

Ultrasonic level measurement is based on the time required by ultrasonic pulses to travel from sensor & surface of liquid & back to sensor. Ultrasonic level transmitters are the best for applications such as slurries, corrosive liquids & waste water. The transmitter provides 4-20 mA DC continuous output with local indication through LCD. The measuring range is available from 0.6 to 8 mtr.

Specification 

 

  • Model: ULT-200
  • Measuring Range: 0.6 to 15 mtr
  • Response Time: Less than 500 mSec
  • Isolated Power Supply: 24 V DC,External
  • Process Connection: 1) 2 inch BSP (M) Threaded - upto 8 mtrs. 2) 3inch BSP (M) Threaded above 8 mtrs. to 15 mtrs.
  • Accuracy: +/- 0.25% of F. S. 

 

LCS 02 - Capacitance Level Switch

LCS 02 - Capacitance Level Switch 

Electronet series LCS-02 are Capacitance Type Level Switches. The vessel wall & probe forms two electrodes.

If the vessel is of non-conductive material, the probe will be double rod type. The distance between the electrodes and surface area of the electrodes remains unchanged. The variable is the depth of the material being measured which represents the dielectric constant between two electrodes. Air and vacuum have relative dielectric constant as 1 and 

that of liquids is greater than 1

The capacitance of the capacitor therefore depends on how much material lies between the probe and vessel wall i.e. whether the probe is covered with or free from material. The capacitance changes with change in level of the material & provides switching output at the desired preset level.

Specification 

 

  • Power/Voltage: 1) 24 V DC 2) 230 V AC, 50 Hz
  • Model Number: LCS - 02
  • Response Time: Less than 1 Sec.
  • Probe Dia: ID 21 mm, OD 25 mm
  • Probe MOC: SS 316 

 

LMS 02 - Magnetic Float Operated Level Switch

Electronet series LMS-02 are Magnetic Float Operated Level Switches. The inbuilt level sensor consists of a float and guide tube made of non-magnetic material to achieve undisturbed magnetic flux.

The float has magnetic system within it and moves along the guide tube which contains glass encapsulated hermitically sealed reed switches. Float follows level and magnetically actuates reed switches and provides switching output at the desired preset level.

Specification 

 

  • Model No.: LMS - 02
  • Power/Voltage: 1) 24 V DC 2) 230 V AC, 50 Hz
  • Temperature Coefficient: +/- 0.01% per degree C
  • Probe Dia: ID 21 mm, OD 25 mm
  • Probe Length: As per requirement (max 3000 mm)
  • Probe MOC: SS 316 

 

ULT 200B - Battery Operated Ultrasonic Level Transmitter

Electronet series ULT-200B is a Battery Operated Ultrasonic Level Transmitters specially designed for non contact type level measurement. Ultrasonic level measurement is based on the time required by ultrasonic pulses to travel from sensor and surface of liquid and back to sensor. Ultrasonic level transmitters are the best for applications such as slurries, corrosive liquids and waste water without obstacle throughout the beam. The transmitter provides local indication through LCD.

The measuring range is available from 0.6 to 12 meters.

Specification 

 

  • Brand: Electronet
  • Model: Ult 200b
  • Measuring Range: 0.6 To 6 Mtr
  • Response Time: Less Than 500 Msec
  • Process Connection: 1) 2 Inch Bsp (M) Threaded 2) Other On Request
  • Accuracy: +/- 0.25% Of F. S. 

 